RFI · Balconies and Balustrades
RFI-022
Thermal break product – is the specified one still acceptable at 2.1 m cantilever?
AnsweredDue 19/10Held by Halbrook
Who is holding it up
Halbrook, Contractor
The answer is in, to review and close
“Confirmed: the heavier unit at all 2.1 m cantilevers”
Knock-on effects
No other item is held up by it.
Parent IRS line
Not linked to an IRS line.
Chases drafted
No chase drafted for this item.
Last chase sent 12/10
Timeline
Corvane was holding the bracket order for the thermal break (). Pellam said the specified unit is fine up to 1.8 m but 2.1 m needs the heavier unit (). Farrow Lune sees no change to the soffit or the balcony finishes (). Pellam confirmed the heavier unit at all 2.1 m cantilevers, with a revised balcony detail to follow ().
October 2026
Actions and chases
Action · DTM 07, point 2.2 · Pellam · new · due 19/10
“Balcony thermal break at the 2.1 m cantilevers (RFI-022): Pellam reviewing; a heavier unit is likely.”
Chase sent 12/10 · Tom Ashworth
“RFI-022: thanks – which unit will it be?”